IB Panels ® is the best SIPS company I have worked with. I am a New Mexico builder and have worked with several SIPS companies and have looked at, talked with, and negotiated with a number of others. IB Panels ® is the clear choice. All phone calls were answered by real people(sometimes the owner) all of whom were friendly and knowledgeable. The sales rep was everything you could ask for. No empty promises were made. The panels were delivered in excellent condition and were of absolutely first class quality. Some minor on-site adjustments were required but they did not detract from the great overall experience of dealing with IBP. We hope to do business with them again. -Curt Clemson-
Do you have a testimonial you would like to add to our list?
|
 |
 |
 |
-Back to Previous Page-
Fasteners:
 |
|
One option of fasteners would be to use 1 1/4 to 2 inch grabber screws. |
| |
 |
|
Another option would be to use 8 penny ring shank nails. |
| |
 |
|
All fasteners need to go through the OSB and into the metal. |
| |
 |
|
Fasteners need to be placed every 6 inches on vertical seams on both sides of the seams (staggered) and on both sides of the panel. |
| |
 |
|
Fasteners need to be placed every 12 inches on the base plates on both sides. |
| |
 |
|
Fasteners need to placed every 6 inches on the primary top plate and on the secondary top plate. You will need to stagger the fasteners so that there is 3 inches between the fastener for the primary plate and the fastener for the secondary plate. |
| |
|
 |
 |
 |
Contact Us at:
IB Panels ®
PO Box 723
50 West 100 South
Jerome, ID 83338
PH: 208-324-7184
FAX: 208-324-6740
Toll Free: 888-799-1398
News from IB Panels ®
Habitat for Humanity - "Blitz Build" was completed in 108 hours. IB Panels ® were used for the floors and walls. The walls were stood up within 45 minutes. Article 1 - Article 2 - Article 3.
 View This Home
Up to 50% more energy efficient.
Approximately 40% less on-site labor.
Highly efficient, insulated corners, patented design.
ICC # PFC 5361
Oregon Registration # M397
Quality Control Agency - PFS Corporation
Madison, Wisconsin #98-33


|
 |
 |